62 AC LOSS REPORT CODE
| [00] See box on previous page.
63 LOW BAT REPORT CODE
| [00] See box on previous page.
64 TEST REPORT CODE
| [00] See box on previous page. Use Scheduling mode to set periodic
test reports, or use the following key commands:
Each mode sets schedule 32 (FA168CPS) or installer code +[#] + [0] + 0 = test report sent every 24 hours
schedule 08 (FA148CP) to the stated installer code +[#] + [0] + 1 = test report sent once per week
repeat option; first test report sent 12 hours after command. installer code +[#] + [0] + 2 = test report sent every 28 days
65
OPEN REPORT CODE
[0,0,0] See box above.
Part. 1 Part. 2 Common
66 ARM AWAY/STAY RPT CODE
[0,0,0,0,0,0]
See box above.
Away Stay Away Stay Away Stay
Part. 1 Part. 2 Common
67 RF XMTR LOW BAT REPORT CODE
| [00] See box on previous page.
UL: must be enabled if wireless devices are used
68 CANCEL REPORT CODE
| [00] See box on previous page. SIA-Compliant Controls: [10] Report enabled.
69 RECENT CLOSING REPORT CODE
| [11] SIA-Compliant Controls: Always enabled. Field does not apply to other controls.
RESTORE REPORT CODES (
70 –
76)
70 ALARM RESTORE RPT CODE
[0] See box on previous page.
71 TROUBLE RESTORE RPT CODE
| [00] See box on previous page.
72 BYPASS RESTORE RPT CODE
| [00] See box on previous page.
73 AC RESTORE RPT CODE
| [00] See box on previous page.
74 LOW BAT RESTORE RPT CODE
| [00] See box on previous page.
75 RF XMTR LO BAT RST RPT CODE
| [00] See box on previous page.
UL: must be enabled if wireless devices are used
76 TEST RESTORE RPT CODE
| [00] See box on previous page.
OUTPUT AND SYSTEM SETUP (
77 –
93)
77 DAYLIGHT SAVINGS TIME
START/END MONTH
| [4][10]
0 = Disabled
1-12 = January-September (1 = Jan, 2 = Feb, etc)
#+10 = October; #+11 = November; #+12 = December
78 DAYLIGHT SAVINGS TIME
START/END WEEKEND
| [1][5]
0 = disabled, 1 = first, 2 = second, 3 = third
4 = fourth, 5 = last, 6 = next to last, 7 = third to last
79, *80, *81, *82 MENU MODES
These are Menu Mode commands, not data fields, for Output Device Mapping, Output
Programming, Zone List Programming, and Alpha Programming respectively. See
page 2 and their respective sections in the Installation and Setup Guide for procedures.
84 AUTO STAY ARM
[3]
0 = no, 1 = partition 1 only
2 = partition 2 only, 3 = both partitions
85 CROSS ZONE TIMER
This option not for use in UL installations.
[0]
(assign cross zones on
zone list 4, using *81 Menu
mode)
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min
1 = 30 seconds 7 = 3 min #+13 = 10 min
2 = 45 seconds 8 = 4 min #+14 = 12 min
3 = 60 seconds 9 = 5 min #+15 = 15 min
4 = 90 seconds #+10 = 6 min
5 = 2 minutes #+11 = 7 min
86 CANCEL VERIFY KEYPAD DISPLAY
[1]
0 = no, 1 = yes
87 MISC. FAULT DELAY TIME
(used with Configurable Zone Types “digit 6”)
[0]
UL: may only be used on
non-burglar alarm/ non-fire
alarm zones when used in
fire and/or UL burglar alarm
installation
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min
1 = 30 seconds 7 = 3 min #+13 = 10 min
2 = 45 seconds 8 = 4 min #+14 = 12 min
3 = 60 seconds 9 = 5 min #+15 = 15 min
4 = 90 seconds #+10 = 6 min
5 = 2 minutes #+11 = 7 min
88 PROGRAM MODE LOCKOUT
OPTIONS
[0]
0 = standard *98 installer code lockout (reentry only by
downloader or [] + [#] within 50 secs after power up)
1 = lockout [] + [#] reentry after *98 exit (reenter via
installer code or downloader only)
2 = not used
3 = lockout all local programming after *98 exit (reentry
via downloader only)
89 EVENT LOG FULL REPORT CODE
| [00]
See box on previous page for report code entries.
Zobrazit stránku 4